Remove the Front LED Indicator Module

  1. Prepare the server for service.
    1. Power off the server and disconnect the power cords from the power supplies.

      See Powering Down the Server.

    2. Extend the server to the maintenance position.

      See Extend the Server to the Maintenance Position.

    3. Attach an antistatic wrist strap to your wrist, and then to a metal area on the chassis.

      See Take Antistatic Measures.

  2. Using a Philips screwdriver, remove the two screws that secure the front indicator module (FIM) assembly to the server chassis [1].
    image:Figure showing how to remove the front indicator module (FIM) from
                            the server.
  3. Carefully slide the FIM assembly toward the front of the server to remove it from the chassis [2].
  4. Using a Phillips screwdriver, remove the two screws that secure the plastic temperature sensor housing to the FIM assembly, and then detach the housing from the FIM assembly [2].

    Note -  You do not need to remove the temperature sensor from the housing.
  5. Disconnect the FIM cable from the FIM assembly and set the FIM assembly aside [3].
  6. Continue to Install the Front LED Indicator Module.