Environmental Requirements
The following table lists the specifications for temperature, humidity, altitude,
acoustic noise, vibration, and shock.
 | Caution -
Set conditions to the optimal temperature and humidity ranges to minimize the
chance of downtime due to component failure. Operating your Oracle Server X7-8 for
extended periods at or near the operating range limits, or installing it in an
environment when it remains at or near nonoperating range limits could significantly
increase hardware component failure.
|
|
|
|
Ambient temperature (Does not apply to removable media)
|
Note -
Maximum ambient operating temperature is derated by 1 degree C
per every 300 meters elevation beyond 900 meters, up to a
maximum altitude of 3,000 meters elevation.
|
–40˚F to 154˚F
(–40˚C to 68˚C)
|
Relative humidity
|
-
10% to 90% noncondensing, short term 25˚F to
113˚F (–5˚C to
55˚C)
-
5% to 90% noncondensing, but not to exceed 0.024 kg of
water per kg of dry air (0.053 lbs water/2.205 lbs dry
air)
|
Up to 93% noncondensing 95˚F (35˚C) maximum wet
bulb
|
Altitude
|
Maximum 9,840 feet (3,000 meters) at 95˚F (35˚C)
Note -
In China markets, regulations might limit installations to a
maximum altitude of 6,562 feet (2,000 meters).
|
Maximum 39,370 feet (12,000 meters)
|
Acoustic Noise
|
|
Not applicable
|
Vibration
|
IEC 60068-2-6 Test FC
|
IEC 60068-2-6 Test FC
|
Shock
|
3 Gs, 11 ms half-sine
IEC 60068-2-27 Test Ea
|
Roll-off: 1.25-inch roll-off free fall, front to back rolling
directions
Threshold: 13 mm threshold height at 0.65 m/s impact
velocity
ETE-1010-02 Rev A
|
|