Library Dimensions and Weights
Review the dimensions and weights of library modules and components to ensure the library has proper clearances at the installation site.
- Base Module Measurements
- Drive Module Measurements
- Cartridge Module Measurements
- Access Module Measurements
- Covers, Doors, and Service Clearances
- Shipping Weights and Dimensions
Figure 1-8 Clearances and Dimensions (Side View of SL4000)

- Base and Drive Module rear service clearance
- Base and Drive Module front service clearance
- Access Module service clearance
- Weight pad adjustment range
Figure 1-9 Clearances and Dimensions (Overhead View of Example SL4000 Layouts)

- Side cooling area
- Side cover
- Nozzle cutout for fire suppression system
- Base Module and Drive Module service clearance (light gray areas)
- Access Module service clearance (dark gray areas)
- Weight distribution pad
Covers, Doors, and Service Clearances
Dimension | Measurement |
---|---|
Height |
190.3 cm (74.9 in.) frame only |
Door thickness |
Front: 1.9 cm (0.75 in.) Back: 4.5 cm (1.75 in.) |
Door latches |
2.53 cm (0.9 in.) |
Service clearance |
Front: 45.7 cm (18 in.) for Base and Drive Module only, 59.7 cm (23.5 in.) for Access Module Back: 81 cm (32 in.) for Base and Drive Module only Side: 5 cm (2 in.) for cooling, 45.7 cm (18.0 in.) for install |
Side cover |
7.4 cm (2.9 in.) width 18.5 kg (41 lb) each |
Shipping Weights and Dimensions
The SL4000 library modules and other components are shipped on pallets. The table below lists each module and its shipping specifications.
If equipment on a pallet must be transported on elevators, the elevator cars must be capable of safely handling the weight.
Component | Height | Width | Depth | Weight |
---|---|---|---|---|
Base Module |
213.3 cm (84 in.) |
99 cm (39 in.) |
159.3 cm (62.7 in.) |
433 kg (954 lb) |
Drive Module |
213.3 cm (84 in.) |
99 cm (39 in.) |
159.3 cm (62.7 in.) |
381 kg (839 lb) |
Cartridge/Parking Module |
215 cm (84.7 in.) |
99 cm (39 in.) |
100.7 cm (39.6 in.) |
250 kg (552 lb) |
Access Module |
215 cm (84.7 in.) |
113 cm (44.6 in.) |
100.7 cm (39.6 in.) |
290 kg (640 lb) |
LTO drive tray |
32 cm (12.6 in.) |
31 cm (12.2 in.) |
66 cm (26 in.) |
9.5 kg (20.9 lbs) |
T10000 drive tray |
34 cm (13.4 in.) |
31 cm (12.2 in.) |
66 cm (26 in.) |
10.5 kg (23.1 lbs) |
Drive array |
48.3 cm (19 in.) |
65.5 cm (25.75 in.) |
83.8 cm (33 in.) |
24.5 kg (54 lbs) |
CAP |
32 cm (12.6 in.) |
39.4 cm (15.5 in.) |
135.4 cm (54.5 in.) |
32.7 kg (72 lbs) |
Redundant robot |
63.2 cm (24.9 in.) |
46.7 cm (18.4 in.) |
196.9 cm (77.5 in.) |
35 kg (77 lbs) |
PDU |
41.3 cm (16.25 in.) |
32.7 cm (12.9 in.) |
44.7 cm (17.6 in.) |
7.7 kg (17 lbs) |
Power Supply |
14 cm (5.5 in.) |
29 cm (11.4 in.) |
40 cm (15.7 in.) |
4 kg (8.8 lbs) |
Power Cord |
10.2 cm (4 in.) |
31.8 cm (12.5 in.) |
31.8 cm (12.5 in.) |
1.6 kg (3.5 lbs) |
Pallets have a pallet-ramp design to provide safe removal of the module at the customer site. The modules have wheels to allow for easy positioning. Once positioned, the installer must raise the modules from their wheel-base to rest upon weight-plates for stability and leveling.