1.7.1.5 High-Voltage 15 kVA Single Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan
Note:
The following specifications are for a single PDU. Every Oracle Exadata Rack configuration contains two PDUs.Table 1-31 Specifications for each High-Voltage 15 kVA Single Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan
Specification | Value |
---|---|
Number of Inputs | 3 x 25A 1ph |
Voltage | 220 - 240 VAC |
Frequency | 50/60 Hz |
Current | 25A maximum (per input) |
Power Rating | 15 kVA |
Output Current | 72A (3 x 24A) |
Outlets | 42 x C13, 6 x C19 |
Outlet Groups | 6 |
Group Protection (UL489 1-pole circuit breaker) | 20A |
Data Center Receptacle | IEC309 32A 3 PIN 250 VAC IP44 |
Note:
The high-voltage 15 kVA single phase PDU is no longer available. The high-voltage 22kVA single phase PDU is the recommended replacement.Parent topic: PDU Power Requirements