1.7.1.6 High-Voltage 22 kVA Single Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan
Note:
The following specifications are for a single PDU. Every Oracle Exadata Rack configuration contains two PDUs.Table 1-32 Specifications for each High-Voltage 22 kVA Single Phase PDUs for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan
Specification | Value |
---|---|
Number of Inputs | 3 |
Source Voltage | 200-240V |
Frequency | 50/60 Hz |
Max Line Current | 32A |
Phase Current | N/A |
Nominal Power Rating | 22kVA |
Recommended Circuit Breaker | 30A |
Outlets | 42 x C13, 6 x C19 |
Outlet Groups | 6 |
Max Group Current | 20A |
Output Voltage | 200-240V |
Data Center Receptacle | 1ph 2W + ground 32A IEC60309 3P 6H 230V |
Parent topic: PDU Power Requirements