1.7.1.4 Low-Voltage 24 kVA Three Phase PDU for North America, South America, Japan and Taiwan
Note:
The following specifications are for a single PDU. Every Oracle Exadata Rack configuration contains two PDUs.Table 1-30 Specifications for each Low-Voltage 24 kVA Three Phase PDU for North America, South America, Japan and Taiwan
Specification | Value |
---|---|
Number of Inputs | 2 |
Source Voltage | 200-220V |
Frequency | 50/60 Hz |
Max Line Current | 34.6A |
Phase Current | 20A |
Nominal Power Rating | 24kVA |
Recommended Circuit Breaker | 50A |
Outlets | 42 x C13, 6 x C19 |
Outlet Groups | 6 |
Max Group Current | 20A |
Output Voltage | 200-240V |
Data Center Receptacle | 3ph 3W + ground 60A IEC60309 |
Parent topic: PDU Power Requirements