C H A P T E R 4 |
Configuring the Sun Blade 6000 Modular System Management Network |
This chapter describes how to configure the chassis monitoring module (CMM) for access to the Oracle Integrated Lights Out Manager (ILOM).
This section covers topics listed in the following table.
Communicating With CMM ILOM Using the Management Network IP Addresses. |
|
The following topics are covered in this section:
The Integrated Lights Out Manager (ILOM) is a built-in system management tool that enables you to monitor and manage the components installed in the Sun Blade 6000 chassis. The ILOM is accessed through the CMM service processor. For instance, in CMM ILOM, you can configure network information, view and edit hardware configurations, monitor vital system information, and manage user accounts.
The CMM ILOM is accessible through command-line interfaces (CLI), a web interface, and IPMI interfaces.
Some server modules that are installed in the Sun Blade 6000 chassis might use a different management software. See your server module documentation for information on server module management. Storage modules do not have a service processor and do not run ILOM. See your storage module documentation for more information on storage module management.
For more information about the tasks you can perform in the CMM ILOM, see the ILOM documentation listed at ILOM Documentation.
The Sun Blade 6000 modular system ships with one preconfigured CMM ILOM administrator account:
The preconfigured administrator account, known as root, cannot be deleted or changed, other than changing its default password. This account offers built-in administrative privileges (read and write access) to all CMM ILOM functions, features, and commands.
The first time you access ILOM at the CMM level or server module level you need to log in as root with the default password changeme.
After you have logged into CMM ILOM and established network connectivity to the system, change the password associated with the ILOM root account to prevent your system from unauthorized access.
For more information about resetting the ILOM root account password, see Changing the CMM ILOM Root Account Password with CLI.
As of ILOM 3.0.12, the Sun Blade 6000 modular system supports dual-stack IPv4 and IPv6 settings, which enable ILOM to fully operate in an IPv4 and IPv6 network environment. For IPv4 configurations, DHCP is enabled by default, allowing a DHCP server on the network to automatically assign network settings to the CMM. For IPv6 configurations, IPv6 stateless auto-configuration is enabled by default, allowing an IPv6 router on the network to assign the network settings.
In a typical configuration, you will accept these settings assigned by the DHCP server or IPv6 router. The procedures in this section allow you to log in to ILOM to test that the assigned settings are working correctly, and also to change the settings if necessary.
TABLE 4-1 lists the ILOM documentation available for the Sun Blade 6000 modular system for ILOM 3.x or later. Refer to this documentation for further details on using ILOM with the Sun Blade 6000 modular system.
If you are using ILOM 2.x, refer to the documentation at http://docs.sun.com/app/docs/prod/blade.6000mod~ilom2.0#hic.
Sun Integrated Lights Out Manager (ILOM) 3.0 Getting Started Guide |
||
Sun Integrated Lights Out Manager (ILOM) 3.0 Web Interface Procedures Guide |
||
Sun Integrated Lights Out Manager (ILOM) 3.0 CLI Procedures Guide |
||
Sun Integrated Lights Out Manager (ILOM) 3.0 Feature Updates and Release Notes |
||
http://docs.sun.com/app/docs/prod/blade.6000mod~blade6000ilom#hic |
||
Oracle Integrated Lights Out Manager (ILOM) 3.0 Supplement for the Sun Blade 6000 and 6048 Modular Systems |
||
Oracle Integrated Lights Out Manager (ILOM) CMM Administration Guide for Sun Blade 6000 and 6048 Modular Systems |
To set up CMM and server modules with initial network configuration information, you must establish a connection through ILOM to the CMM. Until the CMM has an IP address assigned to it, you must initially use a serial connection to communicate with the CMM. After establishing a serial connection to the CMM, you can choose to configure the CMM and server modules with static or DHCP IP addresses.
This section includes the following topics:
Prior to assigning IP addresses, ensure that you have completed the following installation tasks:
Before you can access the CMM ILOM through the Ethernet NET MGT port, you will need to determine the IP address assigned to the CMM. This section covers the following topics:
The CMM is set to acquire IP addresses through DHCP by default. Follow these instructions when using DHCP to assign IP addresses.
1. Verify that your DHCP server is configured to accept new media access control (MAC) addresses. Refer to the documentation supplied with your DHCP server software.
2. Verify that the Ethernet cable is plugged into the NET MGT port on the active CMM.
3. To obtain the DHCP IP addresses assigned to the CMM, use one of the following methods:
a. Using a serial console attached to the rear panel of the CMM, log into CMM ILOM as the administrator. At the login prompt, type the ILOM administrator username and password.
The default user name is root and the default password is changeme. changeme.
c. To view the network information for the CMM, type the following command:
d. To drill view the IP addresses of each server module, type the following command:
-> show /CH/BLx/SP/network
BLx represents the server module installed in slot BL-0. To specify the target server module, you must specify the slot number of where the module is installed. Server module slots range from 0 to 9.
Note - Storage modules do not have a service processor. If you view storage blade information using /CH/BLx, the SP target is not shown. |
Refer to the DHCP server documentation for details.
Note - Refer to the server module documentation for more information on assigning a DHCP address to a server module SP. |
Follow these instructions when assigning a static IP address to a CMM through a serial connection:
1. Verify that your serial connection to the active CMM is operational.
For information about attaching a serial console to a CMM, see How to Cable the CMM.
2. Log into CMM ILOM as an administrator by entering an administrator user name and password, and then press Enter.
The default user name is root and the default password is changeme.
The default prompt appears (->) and the system is ready for you to run the CLI commands to establish network settings.
3. Type the following command to set the working directory:
4. Use the following commands to specify the IP, netmask, and gateway addresses.
The following procedures are covered in this section:
|
You can only run ILOM CLI commands through the SER MGT port. You cannot run the ILOM web interface through the SER MGT port.
1. Ensure that you have cabled a terminal device to the CMM SER MGT port.
See Cabling the Chassis Monitoring Module (CMM).
2. From your terminal device, log into the CMM ILOM with a valid ILOM user account and password.
The default login account is root and default password is changeme.
Once you are logged in, you communicate with the CMM using the CMM ILOM command line interface. For CLI details, refer to the Sun Integrated Lights Out Manager (ILOM) 3.0 CLI Procedures Guide.
|
Perform this task when you want to access the CMM ILOM through your network. You can perform ILOM CLI or ILOM web interface commands.
1. Ensure that the following conditions are met:
The default login account is root and default password is changeme.
The ILOM -> prompt is displayed.
i. Open a browser and type in the CMM ILOM IP address in the following format:
ii. At the login page, enter your login and password.
The main ILOM page is displayed.
Once you are logged into the CLI or web interface, you can perform a variety of ILOM commands to administer the modular components. Refer to the ILOM documentation for more information. See ILOM Documentation.
|
If you want to change the network settings currently configured for the server module, use the following procedure.
1. Log in to ILOM using one of the methods in How to Log Into the CMM Through the SER MGT Port or How to Log Into the CMM Through the NET MGT Port.
2. Perform the network configuration instructions that apply to your network environment:
3. For IPv4 network configurations, use the cd command to navigate to the /network directory:
-> set pendingipdiscovery=static -> set pendingipaddress=10.8.183.106 -> set pendingipnetmask=255.255.255.0 -> set pendingipgateway=10.8.183.254 -> set commitpending=true |
5. For IPv6 network configurations, use the cd command to navigate to the /CMM/network/ipv6 directory:
6. Type the show command to view the IPv6 network settings configured on the device.
For example, see the following sample output values for the IPv6 properties on a server SP device.
7. To configure an IPv6 auto-configuration option, use the set command to specify the following auto-configuration property values:
Note - The IPv6 configuration options take affect after they are set. You do not need to commit these changes under the /CMM/network target. |
8. Perform the following steps to set a static IPv6 address:
a. To set a static IPv6 address, specify the following property values:
b. To commit the pending IPv6 static network parameters, perform the steps in the following table:
9. To test the IPv4 or IPv6 network configuration from ILOM use the Network Test Tools (Ping and Ping6). For details, see How to Test the IPv4 or IPv6 Network Configuration.
|
1. At the CLI prompt, type the show command to view the network test targets and properties.
For example, see the following output the shows the test target properties on a CMM device.
-> show /CMM/network/test Targets: Properties: ping = (Cannot show property) ping6 = (Cannot show property) Commands: cd set show |
2. Use the set ping or set ping6 command to send a network test from the device to a specified network destination.:
Type the set ping= command at the command prompt followed by the IPv4 test destination address. |
||
Type the set ping6= command followed by the IPv6 test destination address. |
To change the changeme password, follow these steps:
1. Log into the CMM ILOM using the SER MGT or NET MGT ports. See Communicating With CMM ILOM Using the Management Network IP Addresses..
2. Change the password for the CMM by typing the following command:
-> set /CMM/users/root password=password
Where password is the new password that you want to assign.
For information about creating new user accounts and assigning a role (privilege) to a user account, see the ILOM documentation listed in ILOM Documentation.