21.6 Three Phase Power Distribution Unit Cabling Tables
This section contains the tables for three phase cabling from each power distribution unit (PDU) to the power supplies configured in each rack. The cables are terminated to PDU-A on the left, and routed to the right to enter CMA, and are bundled in groups of four.
The following tables are in this section:
Table 21-16 shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X2-2 Full Rack.
Table 21-16 Three Phase PDU Cabling for Oracle Exadata Database Machine X2-2 Full Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U41 |
G5-6 |
G2-0 |
2 meters |
U39 |
G5-3 |
G2-3 |
2 meters |
U37 |
G5-0 |
G2-6 |
2 meters |
U35 |
G4-6 |
G1-0 |
2 meters |
U33 |
G4-4 |
G1-2 |
2 meters |
U31 |
G4-2 |
G1-4 |
2 meters |
U29 |
G3-6 |
G0-0 |
2 meters |
U28 |
G4-0 |
G1-6 |
2 meters |
U27 |
G3-5 |
G0-1 |
2 meters |
U26 |
G3-4 |
G0-2 |
2 meters |
U25 |
G3-3 |
G0-3 |
2 meters |
U24 |
G3-1 |
G0-5 |
1 meters |
U23 |
N/A |
G5-0 |
included |
U22 |
G2-5 |
G5-1 |
2 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U19 |
G2-3 |
G5-3 |
2 meters |
U18 |
G2-2 |
G5-4 |
2 meters |
U17 |
G2-1 |
G5-5 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G5-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
U1 |
G0-0 |
G3-6 |
2 meters |
Table 21-17 shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X2-2 Half Rack.
Table 21-17 Three Phase PDU Cabling for Oracle Exadata Database Machine X2-2 Half Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U24 |
G3-1 |
G0-5 |
1 meters |
U23 |
N/A |
G5-0 |
included |
U22 |
G2-5 |
G5-1 |
2 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U19 |
G2-3 |
G5-3 |
2 meters |
U18 |
G2-2 |
G5-4 |
2 meters |
U17 |
G2-1 |
G5-5 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G5-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
U1 |
G0-0 |
G3-6 |
2 meters |
Table 21-18 shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X2-2 Quarter Rack.
Table 21-18 Three Phase PDU Cabling for Oracle Exadata Database Machine X2-2 Quarter Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U24 |
G3-1 |
G0-5 |
1 meters |
U23 |
N/A |
G5-0 |
included |
U22 |
G2-5 |
G5-1 |
2 meter |
U21 |
G3-0 |
G0-6 |
2 meters |
U20 |
G2-4 |
G5-2 |
2 meters |
U17 |
G2-1 |
G5-5 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U6 |
G0-6 |
G3-0 |
2 meters |
U4 |
G0-4 |
G3-2 |
2 meters |
U2 |
G0-2 |
G3-4 |
2 meters |
U1 |
G0-0 |
G3-6 |
2 meters |
Table 21-19 shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X2-8 Full Rack.
Table 21-19 Three Phase PDU Cabling for Oracle Exadata Database Machine X2-8 Full Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U41 |
G5-5 |
G2-1 |
2 meters |
U39 |
G5-4 |
G2-2 |
2 meters |
U37 |
G5-2 |
G2-4 |
2 meters |
U35 |
G5-1 |
G2-5 |
2 meters |
U33 |
G5-0 |
G2-6 |
2 meters |
U31 |
G4-6 |
G1-0 |
2 meters |
U29 |
G4-4 |
G1-2 |
2 meters |
U24 |
G4-1 |
G1-5 |
1 meter |
U24 |
G3-6 |
G0-0 |
1 meter |
U23 |
G3-3 |
G0-3 |
2 meters |
U22 |
G3-0 |
G0-6 |
2 meters |
U21 |
G2-5 |
G5-1 |
2 meters |
U16 |
G2-1 |
G5-5 |
1 meter |
U16 |
G1-6 |
G4-0 |
1 meter |
U14 |
G1-3 |
G4-3 |
2 meters |
U12 |
G1-0 |
G4-6 |
2 meters |
U10 |
G0-6 |
G3-0 |
2 meters |
U8 |
G0-5 |
G3-1 |
2 meters |
U6 |
G0-4 |
G3-2 |
2 meters |
U4 |
G0-2 |
G3-4 |
2 meters |
U2 |
G0-1 |
G3-5 |
2 meters |
U1 |
G0-0 |
G3-6 |
2 meters |