18.4 Single Phase Power Distribution Unit Cabling Tables
This section contains the tables for single phase cabling from each power distribution unit (PDU) to the power supplies configured in each rack. The cables are terminated to PDU-A on the left, and routed to the right to enter CMA, and are bundled in groups of four.
The following tables are in this section:
-
Table 18-9 Single Phase PDU Cabling for Oracle Exadata Database Machine X6-2 and X5-2 Full Rack
-
Table 18-10 Single Phase PDU Cabling for Oracle Exadata Database Machine X6-2 and X5-2 Half Rack
-
Table 18-11 Single Phase PDU Cabling for Oracle Exadata Database Machine X6-2 and X5-2 Quarter Rack
-
Table 18-12 Single Phase PDU Cabling for Oracle Exadata Database Machine X5-8 and X6-8 Full Rack
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X6-2 and X5-2 Full Rack.
Table 18-9 Single Phase PDU Cabling for Oracle Exadata Database Machine X6-2 and X5-2 Full Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U42 |
G3-6 |
G2-0 |
2 meters |
U41 |
G4-5 |
G1-1 |
2 meters |
U40 |
G5-4 |
G0-2 |
2 meters |
U39 |
G5-6 |
G0-0 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-1 |
G0-5 |
2 meters |
U33 |
G5-0 |
G0-6 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-3 |
G1-3 |
2 meters |
U27 |
G4-2 |
G1-4 |
2 meters |
U26 |
G4-1 |
G1-5 |
2 meters |
U25 |
G3-5 |
G2-1 |
2 meters |
U24 |
G4-0 |
G1-6 |
2 meters |
U23 |
G3-3 |
G2-3 |
2 meters |
U22 |
G3-1 |
G2-5 |
2 meters |
U21 |
G3-0 (Cisco PS-2) |
G2-6 (Cisco PS-1) |
2 meters |
U20 |
G1-5 |
G4-1 |
2 meters |
U19 |
G2-3 |
G3-3 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U17 |
G2-1 |
G3-5 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X6-2 and X5-2 Half Rack.
Table 18-10 Single Phase PDU Cabling for Oracle Exadata Database Machine X6-2 and X5-2 Half Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G2-5 |
2 meters |
U21 |
G3-0 (Cisco PS-2) |
G2-6 (Cisco PS-1) |
2 meters |
U20 |
G1-5 |
G4-1 |
2 meters |
U19 |
G2-3 |
G3-3 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U17 |
G2-1 |
G3-5 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X6-2 and X5-2 Quarter Rack.
Table 18-11 Single Phase PDU Cabling for Oracle Exadata Database Machine X6-2 and X5-2 Quarter Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G2-5 |
2 meters |
U21 |
G3-0 (Cisco PS-2) |
G2-6 (Cisco PS-1) |
2 meters |
U20 |
G1-5 |
G4-1 |
2 meters |
U17 |
G2-1 |
G3-5 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Database Machine X5-8 and X6-8 Full Rack.
Table 18-12 Single Phase PDU Cabling for Oracle Exadata Database Machine X5-8 and X6-8 Full Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U41 |
G5-6 |
G0-0 |
2 meters |
U39 |
G5-4 |
G0-2 |
2 meters |
U37 |
G5-2 |
G0-4 |
2 meters |
U35 |
G5-0 |
G0-6 |
2 meters |
U33 |
G4-6 |
G1-0 |
2 meters |
U31 |
G4-3 |
G1-3 |
2 meters |
U29 |
G3-6 |
G2-0 |
2 meters |
U24 |
G4-7 (C19) (ACO) |
G1-7 (C19) (AC1) |
1 meter |
U24 |
G2-7 (C19) (AC2) |
G3-7 (C19) (AC3) |
1 meter |
U23 |
G3-1 |
G2-5 |
2 meters |
U22 |
G2-6 (PS-2) |
G3-0 (PS-1) |
2 meters |
U21 |
G3-0 |
G2-6 |
2 meters |
U16 |
G3-7 (C19) (AC0) |
G2-7 (C19) (AC1) |
1 meter |
U16 |
G1-7 (C19) (AC2) |
G4-7 (C19) (AC3) |
1 meter |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-3 |
G4-3 |
2 meters |
U10 |
G1-0 |
G4-6 |
2 meters |
U8 |
G0-6 |
G5-0 |
2 meters |
U6 |
G0-4 |
G5-2 |
2 meters |
U4 |
G0-3 |
G5-3 |
2 meters |
U2 |
G0-1 |
G5-5 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |