24.4 Single Phase Power Distribution Unit Cabling Tables
These tables show the cabling routes from each single-phase power distribution unit (PDU) to the power supplies configured in each Oracle Exadata Storage Expansion Rack.
The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.
-
Table 24-17 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8M-2
-
Table 24-18 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8-2
-
Table 24-19 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X7-2
-
Table 24-20 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X6-2
-
Table 24-21 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X5-2
-
Table 24-22 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack
-
Table 24-23 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack
-
Table 24-24 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack
-
Table 24-25 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
-
Table 24-26 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
-
Table 24-27 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X8M-2.
Table 24-17 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8M-2
Rack Unit | PS | PDU-A | PDU-B/PS1 | Cable Length |
---|---|---|---|---|
U42 |
PS0 |
G5-3 |
G0-3 |
2 meters |
U41 |
PS0 |
G5-5 |
G0-1 |
2 meters |
U40 |
PS0 |
G5-6 |
G0-0 |
2 meters |
U39 |
PS0 |
G3-6 |
G2-0 |
2 meters |
U37 |
PS0 |
G3-0 |
G2-6 |
2 meters |
U35 |
PS0 |
G5-4 |
G0-2 |
2 meters |
U33 |
PS0 |
G4-1 |
G1-5 |
2 meters |
U31 |
PS0 |
G5-2 |
G0-4 |
2 meters |
U29 |
PS0 |
G5-1 |
G0-5 |
2 meters |
U27 |
PS0 |
G4-3 |
G1-3 |
2 meters |
U26 |
PS0 |
G4-6 |
G1-0 |
2 meters |
U25 |
PS0 |
G4-5 |
G1-1 |
2 meters |
U24 |
PS0 |
G4-2 |
G1-4 |
2 meters |
U23 |
PS0 |
G4-0 |
G1-6 |
2 meters |
U22 |
PS2 |
G1-6 |
G4-0 |
2 meters |
U21 |
PS2 |
G1-5 |
G4-1 |
2 meters |
U20 |
PS2 |
G1-2 |
G4-4 |
2 meters |
U19 |
PS0 |
G3-2 |
G2-4 |
2 meters |
U18 |
PS0 |
G2-6 |
G3-0 |
2 meters |
U17 |
PS0 |
G0-6 |
G5-0 |
2 meters |
U16 |
PS0 |
G0-3 |
G5-3 |
2 meters |
U14 |
PS0 |
G2-3 |
G3-3 |
2 meters |
U12 |
PS0 |
G2-4 |
G3-2 |
2 meters |
U10 |
PS0 |
G2-0 |
G3-6 |
2 meters |
U8 |
PS0 |
G2-5 |
G3-1 |
2 meters |
U6 |
PS0 |
G0-0 |
G5-6 |
2 meters |
U4 |
PS0 |
G0-1 |
G5-5 |
2 meters |
U2 |
PS0 |
G1-0 |
G4-6 |
2 meters |
U1 |
PS2 |
G3-5 |
G2-1 |
3 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X8-2.
Table 24-18 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X8-2
Rack Unit | PDU-A/PSU 0 | PDU-B/PSU 1 | Cable Length |
---|---|---|---|
U42 |
G3-5 |
G2-1 |
2 meters |
U41 |
G5-5 |
G0-1 |
2 meters |
U40 |
G3-3 |
G2-3 |
2 meters |
U39 |
G5-4 |
G0-2 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-2 |
G0-4 |
2 meters |
U33 |
G4-4 |
G1-2 |
2 meters |
U31 |
G4-3 |
G1-3 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-0 |
G2-6 |
2 meters |
U26 |
G5-1 |
G0-5 |
2 meters |
U25 |
G5-0 |
G0-6 |
2 meters |
U24 |
G4-1 |
G1-5 |
2 meters |
U23 |
G3-6 |
G2-0 |
2 meters |
U22 |
G1-2 |
G4-4 |
2 meters |
U21 |
G0-5 |
G5-1 |
2 meters |
U20 |
G0-4 |
G5-2 |
2 meters |
U19 |
G2-4 |
G3-2 |
2 meters |
U18 |
G1-1 |
G4-5 |
2 meters |
U17 |
G0-3 |
G5-3 |
2 meters |
U16 |
G0-2 |
G5-4 |
2 meters |
U14 |
G2-3 |
G3-3 |
2 meters |
U12 |
G2-2 |
G3-4 |
2 meters |
U10 |
G2-1 |
G3-5 |
2 meters |
U8 |
G2-0 |
G3-6 |
2 meters |
U6 |
G1-0 |
G4-6 |
2 meters |
U4 |
G0-1 |
G5-5 |
2 meters |
U2 |
G0-0 |
G5-6 |
2 meters |
U1 |
G4-0 |
G1-6 |
3 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X7-2.
Table 24-19 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X7-2
Rack Unit | PDU-A/PSU 0 | PDU-B/PSU 1 | Cable Length |
---|---|---|---|
U42 |
G5-5 |
G0-1 |
2 meters |
U41 |
G3-6 |
G2-0 |
2 meters |
U40 |
G5-2 |
G0-4 |
2 meters |
U39 |
G5-6 |
G0-0 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-1 |
G0-5 |
2 meters |
U33 |
G5-0 |
G0-6 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-3 |
G1-3 |
2 meters |
U27 |
G3-5 |
G2-1 |
2 meters |
U26 |
G4-5 |
G1-1 |
2 meters |
U25 |
G4-2 |
G1-4 |
2 meters |
U24 |
G4-1 |
G1-5 |
2 meters |
U23 |
G2-5 |
G3-1 |
2 meters |
U22 |
G1-4 |
G4-2 |
2 meters |
U21 |
G1-3 |
G4-3 |
2 meters |
U20 |
G1-5 |
G4-1 |
2 meters |
U19 |
G2-3 |
G3-3 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U17 |
G1-6 |
G4-0 |
2 meters |
U16 |
G1-2 |
G4-4 |
2 meters |
U14 |
G2-4 |
G3-2 |
2 meters |
U12 |
G2-1 |
G3-5 |
2 meters |
U10 |
G2-0 |
G3-6 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G4-0 |
G1-6 |
3 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X6-2.
Table 24-20 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X6-2
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U42 |
G3-6 |
G2-0 |
2 meters |
U41 |
G4-5 |
G1-1 |
2 meters |
U40 |
G5-4 |
G0-2 |
2 meters |
U39 |
G5-6 |
G0-0 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-0 |
G0-6 |
2 meters |
U33 |
G4-6 |
G1-0 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-6 |
G2-0 |
2 meters |
U25 |
G3-5 |
G2-1 |
2 meters |
U23 |
G3-3 |
G2-3 |
2 meters |
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Rack X5-2.
Table 24-21 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Rack X5-2
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U41 |
G4-5 |
G1-1 |
2 meters |
U39 |
G5-6 |
G0-0 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-0 |
G0-6 |
2 meters |
U33 |
G4-6 |
G1-0 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-6 |
G2-0 |
2 meters |
U25 |
G3-5 |
G2-1 |
2 meters |
U23 |
G3-3 |
G2-3 |
2 meters |
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack.
Table 24-22 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Full Rack, and Oracle Exadata Storage Expansion X3-2 Full Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U39 |
G5-6 |
G0-0 |
2 meters |
U37 |
G5-3 |
G0-3 |
2 meters |
U35 |
G5-0 |
G0-6 |
2 meters |
U33 |
G4-6 |
G1-0 |
2 meters |
U31 |
G4-4 |
G1-2 |
2 meters |
U29 |
G4-2 |
G1-4 |
2 meters |
U27 |
G3-6 |
G2-0 |
2 meters |
U25 |
G3-5 |
G2-1 |
2 meters |
U23 |
G3-3 |
G2-3 |
2 meters |
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack.
Table 24-23 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Half Rack, and Oracle Exadata Storage Expansion X3-2 Half Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack.
Table 24-24 Single Phase PDU Cabling for Oracle Exadata Storage Expansion X4-2 Quarter Rack, and Oracle Exadata Storage Expansion X3-2 Quarter Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G2-5 |
2 meters |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 24-25 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U41 |
G5-6 |
G0-0 |
2 meters |
U39 |
G5-3 |
G0-3 |
2 meters |
U37 |
G5-0 |
G0-6 |
2 meters |
U35 |
G4-6 |
G1-0 |
2 meters |
U33 |
G4-4 |
G1-2 |
2 meters |
U31 |
G4-2 |
G1-4 |
2 meters |
U29 |
G3-6 |
G2-0 |
2 meters |
U27 |
G3-5 |
G2-1 |
2 meters |
U25 |
G3-3 |
G2-3 |
2 meters |
U24 |
G3-1 |
G2-5 |
2 meters |
U23 |
N/A |
G3-0 |
included |
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 24-26 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G2-5 |
2 meter |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U18 |
G2-2 |
G3-4 |
2 meters |
U16 |
G1-6 |
G4-0 |
2 meters |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-4 |
G4-2 |
2 meters |
U10 |
G1-2 |
G4-4 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |
The following table shows the cable connections from the PDUs to the rack units in Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers.
Table 24-27 Single Phase PDU Cabling for Oracle Exadata Storage Expansion Quarter Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U22 |
G3-1 |
G2-5 |
2 meters |
U21 |
G3-0 |
G2-6 |
2 meters |
U20 |
G2-4 |
G3-2 |
2 meters |
U8 |
G1-0 |
G4-6 |
2 meters |
U6 |
G0-6 |
G5-0 |
2 meters |
U4 |
G0-4 |
G5-2 |
2 meters |
U2 |
G0-2 |
G5-4 |
2 meters |