Cooling Zones

The server has five front-to -back cooling zones. The cooling zones are numbered from left to right (from the front of the server) as zone 0 to zone 4.

The airflow cooling in zone 0 is concentrated through the power supplies (PSs) and is provided by the internal PS fan modules. In a 4-socket configuration, zones 1 and 2 operate independently from zones 3 and 4.

The fan modules (FM0- FM7) provide the airflow for cooling zones 1-4. Each zone has a pair of dedicated FMs:

  • Zone 1 airflow cooling is concentrated on the CPU modules (CMODs) CMOD0 and CMOD1 and is provided by FM0 and FM1.

  • Zone 2 airflow cooling is concentrated on CMOD2 and CMOD3 and is provided by FM2 and FM3.

  • Zone 3 airflow cooling is concentrated on CMOD4 and CMOD5 and is provided by FM4 and FM5.

  • Zone 4 airflow is concentrated on CMOD6 and CMOD7 and is provided by FM6 and FM7.

Note:

In a four-CMOD server configuration, the fan modules for cooling zones 3 and 4 are not powered. However, to maintain the integrity of the cooling subsystem, FMs 4-7 must be installed in the server.


An illustration showing the server cooling zones.
Call Out Description Cooling provided by:

0

Zone 0: Power supplies

Four power supply fans

1

Zone 1: CMOD0 and CMOD1

FM0 and FM1

2

Zone 2: CMOD2 and CMOD3

FM2 and FM3

3

Zone 3: CMOD4 and CMOD5

FM4 and FM5

4

Zone 4: CMOD6 and CMOD7

FM6 and FM7