Environment Monitor MIB (ap-env-monitor.mib)
The following table describes the SNMP GET query names for the Environment Monitor MIB (ap-env-monitor.mib).
To form the OID for an object, append the value in the OID column to 1.3.6.1.4.1.9148.3.3.1. For example, the OID for apEnvMonI2CState is 1.3.6.1.4.1.9148.3.3.1.1.
SNMP GET Query Name | OID | Description |
---|---|---|
apEnvMonI2CState | 1 | State of the environmental monitor located
in the chassis. Values are:
|
The apEnvMonVoltageStatusEntry object has the OID 1.3.6.1.4.1.9148.3.3.1.2.1.1. This object is deprecated.
The apEnvMonTemperatureStatusEntry object has the OID 1.3.6.1.4.1.9148.3.3.1.3.1.1.
To form the OID for an object, append the value in the OID column to 1.3.6.1.4.1.9148.3.3.1.3.1.1. For example, the OID for apEnvMonTemperatureStatusType is 1.3.6.1.4.1.9148.3.3.1.3.1.1.2.
SNMP GET Query Name | OID | Description |
---|---|---|
apEnvMonTemperatureStatusType | 2 | Indicates the entity being monitored for
temperature. Values are:
|
apEnvMonTemperatureStatusDescr | 3 | Description of the temperature being monitored. It has the value of the Main Board PROM Temperature (in Celsius). |
apEnvMonTemperatureStatusValue | 4 | The current temperature of the main board PROM in Celsius. |
apEnvMonTemperatureState | 5 | Current state of the temperature which can have one of the
following values:
Values specific to 3900/3950/4900:
In general, the critical alarm is sent at 95% of the maximum allowed temperature, the major alarm at 90%, and the minor alarm at 85%. |
apEnvMonTemperatureSlotID | 6 | Slot for which this temperature is found. |
apEnvMonTemperatureSlotType | 7 | Type of module found in this slot. |
The apEnvMonFanStatusEntry object has the OID 1.3.6.1.4.1.9148.3.3.1.4.1.1.
SNMP GET Query Name | Object ID: 1.3.6.1.4.1.9148.3.3.1.4.1.1 + | Description |
---|---|---|
apEnvMonFanStatusType | .2 | Location of the fan, which can have one of
the following values:
11: fan1 12: fan2 13: fan3 14: fan4 |
apEnvMonFanStatusDescr | .3 | Textual description of the fan. |
apEnvMonFanStatusValue | .4 | Current measurement of fan speed in percentage. |
apEnvMonFanState | .5 | Current state of the fan speed which can
have one of the following values:
1: initial. The temperature is at its initial state. 2: normal. The fan speed is normal. 3: minor. The fan speed is between 75% and 90% of the full fan speed 4: major. The fan speed is between 50% and 75% of the full fan speed 5: critical. The fan speed is less than 50% of the full fan speed. 6: shutdown. The system should be shutdown immediately 7: not present. The fan sensor does not exist. 8: not functioning. The fan sensor is not functioning properly. 9: unknown. Cannot obtain information due to an internal error. |
apEnvMonFanState | .6 | Current state of the fan being monitored. |
apEnvMonFanSlotID | .7 | Slot where this fan is found. A zero is returned if this fan is not the type slot. |
The apEnvMonPowerSupplyStatusEntr object has the OID 1.3.6.1.4.1.9148.3.3.1.5.1.1.
SNMP GET Query Name | Object ID: 1.3.6.1.4.1.9148.3.3.1.5.1.1 + | Description |
---|---|---|
apEnvMonPowerSupplyStatusType | .2 | Location of the power supply, which can
have one of the following values:
0: left power supply B 1: right power supply A 3: slot |
apEnvMonPowerSupplyStatusDescr | .3 | Textual description of the power supply. |
apEnvMonPowerSupplyState | .4 | Current state of the power supply. Values:
2: normal. The power supply is normal. 7: not present: The power supply sensor does not exist. |
The apEnvPhyCardStatusEntry object has the OID 1.3.6.1.4.1.9148.3.3.1.6.1.1.
SNMP GET Query Name | Object ID: 1.3.6.1.4.1.9148.3.3.1.6.1.1 + | Description |
---|---|---|
apEnvMonPhyCardStatusDescr | .3 | Textual description of the phy card. |
apEnvMonPhyCardState | .4 | The current state of the phy card. Values:
2: normal 7: not present |