15.4.1 Single Phase PDU Cabling for Oracle Exadata X9M-2 Full Rack
Single phase cabling for the Oracle Exadata X9M-2 Full Rack routes from each power distribution unit (PDU) to the power supplies on each server or switch.
The cables are terminated to PDU-A on the left (when looking at the rear of the rack), and routed to the right to enter the cable management arm (CMA). The cables are bundled in groups of four. The PDU connections list the group and outlet on the PDU. So, for example, G5-5 refers to group 5 outlet 5.
Table 15-5 Single Phase PDU Cabling for Oracle Exadata X9M-2 Full Rack
Rack Slot | PSU 0 to PDU-A Outlet | PSU 1 to PDU-B Outlet | Cable Length |
---|---|---|---|
U42 | G5-6 | G0-0 | 3 meters |
U41 | G4-6 | G1-0 | 3 meters |
U40 | G4-2 | G1-4 | 3 meters |
U39 | G4-4 | G1-2 | 3 meters |
U37 | G1-5 | G4-1 | 3 meters |
U35 | G3-1 | G2-5 | 3 meters |
U33 | G1-3 | G4-3 | 3 meters |
U31 | G3-3 | G2-3 | 3 meters |
U29 | G4-0 | G1-6 | 3 meters |
U27 | G5-2 | G0-4 | 3 meters |
U26 | G0-6 | G5-0 | 3 meters |
U25 | G3-0 | G2-6 | 3 meters |
U24 | G4-1 | G1-5 | 3 meters |
U23 | G5-0 | G0-6 | 3 meters |
U22 | G1-6 | G4-0 | 3 meters |
U21 | G0-4 | G5-2 | 3 meters |
U20 | G0-3 | G5-3 | 3 meters |
U19 | G3-2 | G2-4 | 3 meters |
U18 | G2-5 | G3-1 | 3 meters |
U17 | G1-2 | G4-4 | 3 meters |
U16 | G1-4 | G4-2 | 3 meters |
U14 | G5-3 | G0-3 | 3 meters |
U12 | G5-4 | G0-2 | 3 meters |
U10 | G2-3 | G3-3 | 3 meters |
U08 | G2-4 | G3-2 | 3 meters |
U06 | G2-6 | G3-0 | 3 meters |
U04 | G0-2 | G5-4 | 3 meters |
U02 | G0-5 | G5-1 | 3 meters |
U01 | G4-3 | G1-3 | 3 meters |
Parent topic: Single Phase Power Distribution Unit Cabling