17.4.4 Single Phase PDU Cabling for Oracle Exadata Database Machine X7-8 Full Rack
Single phase cabling for the Oracle Exadata Database Machine X7-8 Full Rack routes from each power distribution unit (PDU) to the power supplies.
The cables are terminated to PDU-A on the left, and routed to the right to enter CMA, and are bundled in groups of four.
Table 17-8 Single Phase PDU Cabling for Oracle Exadata Database Machine X7-8 Full Rack
Rack Unit | PDU-A/PS-00 | PDU-B/PS-01 | Cable Length |
---|---|---|---|
U41 |
G5-6 |
G0-0 |
2 meters |
U39 |
G5-4 |
G0-2 |
2 meters |
U37 |
G5-2 |
G0-4 |
2 meters |
U35 |
G5-0 |
G0-6 |
2 meters |
U33 |
G4-6 |
G1-0 |
2 meters |
U31 |
G4-3 |
G1-3 |
2 meters |
U29 |
G3-6 |
G2-0 |
2 meters |
U24 |
G4-7 (C19) (ACO) |
G1-7 (C19) (AC1) |
1 meter |
U24 |
G2-7 (C19) (AC2) |
G3-7 (C19) (AC3) |
1 meter |
U23 |
G3-1 |
G2-5 |
2 meters |
U22 |
G2-6 (PS-2) |
G3-0 (PS-1) |
2 meters |
U21 |
G3-0 |
G2-6 |
2 meters |
U16 |
G3-7 (C19) (AC0) |
G2-7 (C19) (AC1) |
1 meter |
U16 |
G1-7 (C19) (AC2) |
G4-7 (C19) (AC3) |
1 meter |
U14 |
G2-0 |
G3-6 |
2 meters |
U12 |
G1-3 |
G4-3 |
2 meters |
U10 |
G1-0 |
G4-6 |
2 meters |
U8 |
G0-6 |
G5-0 |
2 meters |
U6 |
G0-4 |
G5-2 |
2 meters |
U4 |
G0-3 |
G5-3 |
2 meters |
U2 |
G0-1 |
G5-5 |
2 meters |
U1 |
G0-0 |
G5-6 |
2 meters |
Parent topic: Single Phase Power Distribution Unit Cabling Tables