1.7.1.1 Low-Voltage 15 kVA Single Phase PDU for North America, South America, Japan and Taiwan
Note:
The following specifications are for a single PDU. Every Oracle Exadata Rack configuration contains two PDUs.Table 1-27 Specifications for each Low-Voltage 15 kVA Single Phase PDU for North America, South America, Japan and Taiwan
Specification | Value |
---|---|
Number of Inputs | 3 |
Source Voltage | 200-240V |
Frequency | 50/60 Hz |
Max Line Current | 24A |
Phase Current | N/A |
Nominal Power Rating | 15kVA |
Recommended Circuit Breaker | 30A |
Outlets | 42 x C13, 6 x C19 |
Outlet Groups | 6 |
Max Group Current | 20A |
Output Voltage | 200-240V |
Data Center Receptacle | 1ph 2W + ground 30A NEMA L6-30 |
Parent topic: PDU Power Requirements