1.7.1.8 High-Voltage 24 kVA Three Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan
Note:
The following specifications are for a single PDU. Every Oracle Exadata Rack configuration contains two PDUs.Table 1-34 Specifications for each High-Voltage 24 kVA Three Phase PDU for Europe, the Middle East and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan
Specification | Value |
---|---|
Number of Inputs | 2 |
Source Voltage | 220/380 - 240/415VAC 3Ø |
Frequency | 50/60 Hz |
Max Line Current | 16A |
Phase Current | 16A |
Nominal Power Rating | 24kVA |
Recommended Circuit Breaker | 25A |
Outlets | 42 x C13, 6 x C19 |
Outlet Groups | 6 |
Max Group Current | 18A |
Output Voltage | 220-240V |
Data Center Receptacle | 3ph 4W + ground 32A IEC60309 5P 6h 400V |
Parent topic: PDU Power Requirements