1.2.16 General Environmental Requirements for Single Servers
The environmental requirements for single servers are shown in the following tables.
Table 1-15 Environmental Requirements for Oracle Exadata X11M Single Servers
Environmental Component | Exadata Database Server X11M | Exadata Database Server X11M-Z | Exadata Database Server X11M - 3 TB RAM Configuration | Exadata Storage Server X11M - High Capacity (HC) | Exadata Storage Server X11M - Extreme Flash (EF) | Exadata Storage Server X11M-Z - High Capacity (HC-Z) |
---|---|---|---|---|---|---|
Weight |
24 kg (53 lbs) |
24 kg (53 lbs) |
24 kg (53 lbs) |
33.6 kg (74 lbs) |
27.2 kg (60 lbs) |
28.6 kg (63 lbs) |
Acoustic Noise |
86 dB |
85 dB |
90 dB |
86 dB |
80 dB |
86 dB |
Power |
Maximum: 1.2 kW (1.2 kVA) Typical: 0.8 kW (0.8 kVA) (varies based on application load) |
Maximum: 1.1 kW (1.1 kVA) Typical: 0.8 kW (0.8 kVA) (varies based on application load) |
Maximum: 1.4 kW (1.4 kVA) Typical: 1 kW (1 kVA) (varies based on application load) |
Maximum: 1 kW (1 kVA) Typical: 0.7 kW (0.7 kVA) (varies based on application load) |
Maximum: 0.9 kW (0.9 kVA) Typical: 0.6 kW (0.6 kVA) (varies based on application load) |
Maximum: 0.8 kW (0.8 kVA) Typical: 0.5 kW (0.5 kVA) (varies based on application load) |
Cooling |
At max usage: 4,054 BTU/hour (4,277 kJ/hour) At typical usage: 2,838 BTU/hour (2,994 kJ/hour) |
At max usage: 3,783 BTU/hour (3,991 kJ/hour) At typical usage: 2,648 BTU/hour (2,794 kJ/hour) |
At max usage: 4,705 BTU/hour (4,964 kJ/hour) At typical usage: 3,294 BTU/hour (3,475 kJ/hour) |
At max usage: 3,474 BTU/hour (3,665 kJ/hour) At typical usage: 2,431 BTU/hour (2,565 kJ/hour) |
At max usage: 3,037 BTU/hour (3,204 kJ/hour) At typical usage: 2,126 BTU/hour (2,243 kJ/hour) |
At max usage: 2,570 BTU/hour (2,712 kJ/hour) At typical usage: 1,799 BTU/hour (1,898 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) |
At max usage: Approximately 188 CFM At typical usage: Approximately 131 CFM |
At max usage: Approximately 175 CFM At typical usage: Approximately 123 CFM |
At max usage: Approximately 218 CFM At typical usage: Approximately 152 CFM |
At max usage: Approximately 161 CFM At typical usage: Approximately 113 CFM |
At max usage: Approximately 141 CFM At typical usage: Approximately 98 CFM |
At max usage: Approximately 119 CFM At typical usage: Approximately 83 CFM |
Table 1-16 Environmental Requirements for Oracle Exadata X10M Single Servers
Environmental Component | Database Server X10M | Database Server X10M - 3 TB RAM Configuration | Exadata Storage Server X10M - High Capacity | Exadata Storage Server X10M Eighth Rack - High Capacity | Exadata Storage Server X10M - Extreme Flash | Exadata Storage Server X10M XT Server |
---|---|---|---|---|---|---|
Weight |
23.6 kg (52 lbs) |
24 kg (53 lbs) |
33.6 kg (74 lbs) |
28.6 kg (63 lbs) |
27.2 kg (60 lbs) |
30.8 kg (68 lbs) |
Acoustic Noise |
84 dB |
86 dB |
84 dB |
84 dB |
82 dB |
81 dB |
Power |
Maximum: 1.3 kW (1.3 kVA) Typical: 0.9 kW (0.9 kVA) (varies based on application load) |
Maximum: 1.5 kW (1.5 kVA) Typical: 1 kW (1.1 kVA) (varies based on application load) |
Maximum: 1 kW (1.1 kVA) Typical: 0.7 kW (0.7 kVA) (varies based on application load) |
Maximum: 0.8 kW (0.8 kVA) Typical: 0.5 kW (0.6 kVA) (varies based on application load) |
Maximum: 1 kW (1 kVA) Typical: 0.7 kW (0.7 kVA) (varies based on application load) |
Maximum: 0.4 kW (0.5 kVA) Typical: 0.3 kW (0.3 kVA) (varies based on application load) |
Cooling |
At max usage: 4,299 BTU/hour (4,536 kJ/hour) At typical usage: 3,010 BTU/hour (3,175 kJ/hour) |
At max usage: 5,050 BTU/hour (5,328 kJ/hour) At typical usage: 3,535 BTU/hour (3,729 kJ/hour) |
At max usage: 3,559 BTU/hour (3,755 kJ/hour) At typical usage: 2,491 BTU/hour (2,628 kJ/hour) |
At max usage: 2,634 BTU/hour (2,778 kJ/hour) At typical usage: 1,843 BTU/hour (1,945 kJ/hour) |
At max usage: 3,337 BTU/hour (3,521 kJ/hour) At typical usage: 2,336 BTU/hour (2,464 kJ/hour) |
At max usage: 1,512 BTU/hour (1,595 kJ/hour) At typical usage: 1,058 BTU/hour (1,116 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) |
At max usage: Approximately 199 CFM At typical usage: Approximately 139 CFM |
At max usage: Approximately 234 CFM At typical usage: Approximately 164 CFM |
At max usage: Approximately 165 CFM At typical usage: Approximately 115 CFM |
At max usage: Approximately 122 CFM At typical usage: Approximately 85 CFM |
At max usage: Approximately 154 CFM At typical usage: Approximately 108 CFM |
At max usage: Approximately 70 CFM At typical usage: Approximately 49 CFM |
Table 1-17 Environmental Requirements for X9M-2 Single Servers
Environmental Component | Database Server X9M-2 | Exadata Storage Server X9M-2 - High Capacity | Exadata Storage Server X9M-2 Eighth Rack - High Capacity | Exadata Storage Server X9M-2 - Extreme Flash | Exadata Storage Server X9M-2 XT Server |
---|---|---|---|---|---|
Weight |
20.7 kg (45.6 lbs) |
34.8 kg (76.7 lbs) |
30.6 kg (67.5 lbs) |
27.5 kg (60.6 lbs) |
30.2 kg (66.7 lbs) |
Acoustic Noise |
79 dB |
80 dB |
80 dB |
80 dB |
80 dB |
Power |
Maximum: 0.9 kW (0.9 kVA) Typical: 0.7 kW (0.7 kVA) (varies based on application load) |
Maximum: 0.9 kW (0.9 kVA) Typical: 0.5 kW (0.6 kVA) (varies based on application load) |
Maximum: 0.6 kW (0.6 kVA) Typical: 0.4 kW (0.4 kVA) (varies based on application load) |
Maximum: 0.9 kW (0.9 kVA) Typical: 0.6 kW (0.6 kVA) (varies based on application load) |
Maximum: 0.5 kW (0.5 kVA) Typical: 0.4 kW (0.4 kVA) (varies based on application load) |
Cooling |
At max usage: 3,153 BTU/hour (3,326 kJ/hour) At typical usage: 2,207 BTU/hour (2,328 kJ/hour |
At max usage: 2,883 BTU/hour (3,042 kJ/hour) At typical usage: 2,018 BTU/hour (2,129 kJ/hour) |
At max usage: 2,134 BTU/hour (2,251 kJ/hour) At typical usage: 1,494 BTU/hour (1,576 kJ/hour) |
At max usage: 2,907 BTU/hour (3,067 kJ/hour) At typical usage: 2,035 BTU/hour (2,147 kJ/hour) |
At max usage: 1,720 BTU/hour (1,814 kJ/hour) At typical usage: 1,204 BTU/hour (1,270 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) |
At max usage: Approximately 146 CFM At typical usage: Approximately 102 CFM |
At max usage: Approximately 133 CFM At typical usage: Approximately 93 CFM |
At max usage: Approximately 99 CFM At typical usage: Approximately 69 CFM |
At max usage: Approximately 135 CFM At typical usage: Approximately 94 CFM |
At max usage: Approximately 80 CFM At typical usage: Approximately 56 CFM |
Table 1-18 Environmental Requirements for X8M-2 Single Servers
Environmental Component | Database Server X8M-2 | Exadata Storage Server X8M-2 - High Capacity | Exadata Storage Server X8M-2 Eighth Rack - High Capacity | Exadata Storage Server X8M-2 - Extreme Flash | Exadata Storage Server X8M-2 XT Server |
---|---|---|---|---|---|
Weight |
20.7 kg (45.6 lbs) |
34.8 kg (76.7 lbs) |
30.6 kg (67.5 lbs) |
27.5 kg (60.6 lbs) |
30.2 kg (66.7 lbs) |
Acoustic Noise |
77 dB |
82 dB |
82 dB |
82 dB |
82 dB |
Power |
Maximum: 0.7 kW (0.7 kVA) Typical: 0.5 kW (0.5 kVA) (varies based on application load) |
Maximum: 0.8 kW (0.8 kVA) Typical: 0.5 kW (0.6 kVA) (varies based on application load) |
Maximum: 0.6 kW (0.6 kVA) Typical: 0.4 kW (0.4 kVA) (varies based on application load) |
Maximum: 0.8 kW (0.8 kVA) Typical: 0.6 kW (0.6 kVA) (varies based on application load) |
Maximum: 0.5 kW (0.5 kVA) Typical: 0.3 kW (0.3 kVA) (varies based on application load) |
Cooling |
At max usage: 2,409 BTU/hour (2,541 kJ/hour) At typical usage: 1,686 BTU/hour (1,779 kJ/hour |
At max usage: 2,631 BTU/hour (2,775 kJ/hour) At typical usage: 1,842 BTU/hour (1,943 kJ/hour) |
At max usage: 1,947 BTU/hour (2,054 kJ/hour) At typical usage: 1,363 BTU/hour (1,438 kJ/hour) |
At max usage: 2,730 BTU/hour (2,880 kJ/hour) At typical usage: 1,911 BTU/hour (2,016 kJ/hour) |
At max usage: 1570 BTU/hour (1,656 kJ/hour) At typical usage: 1,099 BTU/hour (1,159 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) |
At max usage: Approximately 112 CFM At typical usage: Approximately 78 CFM |
At max usage: Approximately 122 CFM At typical usage: Approximately 85 CFM |
At max usage: Approximately 90 CFM At typical usage: Approximately 63 CFM |
At max usage: Approximately 126 CFM At typical usage: Approximately 88 CFM |
At max usage: Approximately 73 CFM At typical usage: Approximately 51 CFM |
Table 1-19 Environmental Requirements for X8-2 Single Servers
Environmental Component | Database Server X8-2 | Exadata Storage Server X8-2 - High Capacity | Exadata Storage Server X8-2 Eighth Rack - High Capacity | Exadata Storage Server X8-2 - Extreme Flash | Exadata Storage Server X8-2 XT Server |
---|---|---|---|---|---|
Weight |
20.7 kg (45.6 lbs) |
34.8 kg (76.7 lbs) |
30.6 kg (67.5 lbs) |
27.5 kg (60.6 lbs) |
30.2 kg (66.7 lbs) |
Acoustic Noise |
77 dB |
82 dB |
82 dB |
82 dB |
82 dB |
Power |
Maximum: 0.7 kW (0.7 kVA) Typical: 0.5 kW (0.5 kVA) (varies based on application load) |
Maximum: 0.7 kW (0.7 kVA) Typical: 0.5 kW (0.5 kVA) (varies based on application load) |
Maximum: 0.5 kW (0.5 kVA) Typical: 0.4 kW (0.4 kVA) (varies based on application load) |
Maximum: 0.7 kW (0.7 kVA) Typical: 0.5 kW (0.5 kVA) (varies based on application load) |
Maximum: 0.5 kW (0.5 kVA) Typical: 0.3 kW (0.3 kVA) (varies based on application load) |
Cooling |
At max usage: 2,409 BTU/hour (2,541 kJ/hour) At typical usage: 1,686 BTU/hour (1,779 kJ/hour |
At max usage: 2,317 BTU/hour (2,444 kJ/hour) At typical usage: 1,622 BTU/hour (1,711 kJ/hour) |
At max usage: 1,714 BTU/hour (1,809 kJ/hour) At typical usage: 1,200 BTU/hour (1,266 kJ/hour) |
At max usage: 2,283 BTU/hour (2,408 kJ/hour) At typical usage: 1,598 BTU/hour (1,686 kJ/hour) |
At max usage: 1570 BTU/hour (1,656 kJ/hour) At typical usage: 1,099 BTU/hour (1,159 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) |
At max usage: Approximately 112 CFM At typical usage: Approximately 78 CFM |
At max usage: Approximately 107 CFM At typical usage: Approximately 75 CFM |
At max usage: Approximately 79 CFM At typical usage: Approximately 56 CFM |
At max usage: Approximately 106 CFM At typical usage: Approximately 74 CFM |
At max usage: Approximately 73 CFM At typical usage: Approximately 51 CFM |
Table 1-20 Environmental Requirements for X7-2 Single Servers
Environmental Component | Exadata Storage Server X7-2 - Extreme Flash | Exadata Storage Server X7-2 Eighth Rack - High Capacity | Exadata Storage Server X7-2 - High Capacity | Database Server X7-2 |
---|---|---|---|---|
Weight |
27.5 kg (61 lbs) |
30.1 kg (66.3 lbs) |
34.4 kg (76 lbs) |
20.7 kg (46 lbs) |
Acoustic Noise |
82 dB(A) |
79 dB(A) |
82 dB(A) |
77 dB(A) |
Power |
Maximum: 0.6 kW (0.6 kVA) Typical: 0.4 kW (0.5 kVA) (varies based on application load) |
Maximum: 0.5 kW (0.5 kVA) Typical: 0.3 kW (0.3 kVA) (varies based on application load) |
Maximum: 0.6 kW (0.6 kVA) Typical: 0.4 kW (0.4 kVA) (varies based on application load) |
Maximum: 0.8 kW (0.8 kVA) Typical: 0.5 kW (0.6 kVA) (varies based on application load) |
Cooling |
Maximum: 2,167 BTU/hour (2,286 kJ/hour) Typical: 1,600 BTU/hour (1,378 kJ/hour) |
Maximum: 1,588 BTU/hour (1,676 kJ/hour) Typical: 1,112 BTU/hour (1,173 kJ/hour) |
Maximum: 2,146 BTU/hour (2,264 kJ/hour) Typical: 1,502 BTU/hour (1,585 kJ/hour) |
Maximum: 2,631 BTU/hour (2,775 kJ/hour) Typical: 1,842 BTU/hour (1,943 kJ/hour |
Air flow front-to-back (subject to actual data center environment) |
Maximum: Approximately 100 CFM Typical: Approximately 70 CFM |
Maximum: Approximately 74 CFM Typical: Approximately 51 CFM |
Maximum: Approximately 99 CFM Typical: Approximately 70 CFM |
Maximum: Approximately 122 CFM Typical: Approximately 85 CFM |
Table 1-21 Environmental Requirements for X6-2 Single Servers
Environmental Component | Exadata Storage Server X6-2 - Extreme Flash | Exadata Storage Server X6-2 - High Capacity | Database Server X6-2 |
---|---|---|---|
Weight |
28.1 kg (62 lbs) |
33.1 kg (73 lbs) |
20.4 kg (45 lbs) |
Acoustic Noise |
78 dB(A) |
78 dB(A) |
78 dB(A) |
Power |
Maximum: 0.6 kVA Typical: 0.4 kVA (varies based on application load) |
Maximum: 0.6 kVA Typical: 0.4 kVA (varies based on application load) |
Maximum: 0.665 kW (0.678 kVA) Typical: 0.466 kW (0.475 kVA) (varies based on application load) |
Cooling |
Maximum: 1,866 BTU/hour (1,969 kJ/hour) Typical: 1,307 BTU/hour (1,378 kJ/hour) |
Maximum: 2,006 BTU/hour (2,117 kJ/hour) Typical: 1,404 BTU/hour (1,482 kJ/hour) |
Maximum: 2,269 BTU/hour (2,394 kJ/hour) Typical: 1,588 BTU/hour (1,676 kJ/hour |
Air flow front-to-back (subject to actual data center environment) |
Maximum: Approximately 86 CFM Typical: Approximately 60 CFM |
Maximum: Approximately 93 CFM Typical: Approximately 65 CFM |
Maximum: Approximately 105 CFM Typical: Approximately 74 CFM |
Table 1-22 Environmental Requirements for X5-2 Single Servers
Environmental Component | Exadata Storage Server X5-2 - Extreme Flash | Exadata Storage Server X5-2 - High Capacity | Database Server X5-2 |
---|---|---|---|
Weight |
28.1 kg (62 lbs) |
33.1 kg (73 lbs) |
20.4 kg (45 lbs) |
Acoustic Noise |
78 dB(A) |
78 dB(A) |
78 dB(A) |
Power |
Maximum: 0.6 kVA Typical: 0.4 kVA (varies based on application load) |
Maximum: 0.6 kVA Typical: 0.4 kVA (varies based on application load) |
Maximum: 0.7 kVA Typical: 0.5 kVA (varies based on application load) |
Cooling |
Maximum: 2,037 BTU/hour (2,149 kJ/hour) Typical: 1,426 BTU/hour (1,504 kJ/hour) |
Maximum: 2,000 BTU/hour (2,109 kJ/hour) Typical: 1,400 BTU/hour (1,477 kJ/hour) |
Maximum: 2,481 BTU/hour (2,617 kJ/hour) Typical: 1,736 BTU/hour (1,832 kJ/hour |
Air flow front-to-back (subject to actual data center environment) |
Maximum: Approximately 94 CFM Typical: Approximately 66 CFM |
Maximum: Approximately 93 CFM Typical: Approximately 65 CFM |
Maximum: Approximately 115 CFM Typical: Approximately 80 CFM |
Table 1-23 Environmental Requirements for 8-Socket Servers, Model X4-8 and Later
Environmental Component | Database Server X8M-8 and X9M-8 | Database Server X7-8 and X8-8 | Database Server X5-8 and X6-8 | Database Server X4-8 |
---|---|---|---|---|
Weight |
90.2 kg (198.8 lbs) | 90.2 kg (198.8 lbs) |
93.4 kg (206 lbs) |
93.4 kg (206 lbs) |
Acoustic Noise |
87 dB | 87 dB |
81 dB(A) |
81 dB(A) |
Power |
Maximum: 3.6 kVA Typical: 2.5 kVA (varies based on application load) |
Maximum: 3.6 kVA Typical: 2.5 kVA (varies based on application load) |
Maximum: 3.5 kVA Typical: 2.4 kVA (varies based on application load) |
Maximum: 3.7 kVA Typical: 2.6 kVA (varies based on application load) |
Cooling |
Maximum: 11,953 BTU/hour (12,610 kJ/hour) Typical: 8,367 BTU/hour (8,827 kJ/hour) |
Maximum: 11,942 BTU/hour (12,599 kJ/hour) Typical: 8,360 BTU/hour (8,820 kJ/hour) |
Maximum: 11,601 BTU/hour (12,239 kJ/hour) Typical: 8,121 BTU/hour (8,568 kJ/hour) |
Maximum: 12,284 BTU/hour (12,959 kJ/hour) Typical: 8,599 BTU/hour (9,072 kJ/hour) |
Air flow front-to-back (subject to actual data center environment) |
Maximum: Approximately 553 CFM Typical: Approximately 387 CFM |
Maximum: Approximately 553 CFM Typical: Approximately 387 CFM |
Maximum: Approximately 537 CFM Typical: Approximately 376 CFM |
Maximum: Approximately 569 CFM Typical: Approximately 398 CFM |
Parent topic: General Environmental Requirements