The following tables show estimated run times based on the load in percent of the four approved single phase desktop UPS systems.
The amount of back-up time available is directly related to the VA rating of the UPS utilized. The closer you get to the rated capacity of the UPS, the less back-up time you will have. In addition, make sure to consider battery age.
The runtimes shown in the tables are estimates from PowerVar using new, fully charged batteries at an ambient temperature of 25°C. Depending on the operating environment, UPS batteries lose between 20% and 40% of their capacity after three years. A typical shutdown takes several minutes to perform; therefore, give careful consideration to UPS capacity vs. battery life.
Table 26-5 Estimated Load Times of ABCEG251-11 (Part Number 700247-092-PT)
Load Item | 10% Load Time | 20% Load Time | 30% Load Time | 40% Load Time | 50% Load Time | 60% Load Time | 70% Load Time | 80% Load Time | 90% Load Time | 100% Load Time |
---|---|---|---|---|---|---|---|---|---|---|
Volts |
121 |
122 |
122 |
122 |
122 |
122 |
122 |
122 |
122 |
121 |
Amps |
0.15 |
0.30 |
0.44 |
0.59 |
0.74 |
0.87 |
1.01 |
1.17 |
1.31 |
1.46 |
Watts |
17.5 |
3 |
52.5 |
70 |
87.5 |
105 |
122 |
140 |
158 |
175 |
Run Time (Mins) |
140 |
48 |
56 |
43 |
23 |
19 |
16 |
13 |
12 |
10 |
Table 26-6 Estimated Load Times of ABCEG401-11 (Part Number 700247-093-PT)
Load Item | 10% Load Time | 20% Load Time | 30% Load Time | 40% Load Time | 50% Load Time | 60% Load Time | 70% Load Time | 80% Load Time | 90% Load Time | 100% Load Time |
---|---|---|---|---|---|---|---|---|---|---|
Volts |
122 |
121 |
120 |
121 |
122 |
121 |
121 |
121 |
120 |
119 |
Amps |
0.24 |
0.46 |
0.70 |
0.92 |
1.15 |
1.40 |
1.63 |
1.88 |
2.10 |
2.36 |
Watts |
28 |
5 |
84 |
112 |
140 |
168 |
196 |
224 |
252 |
280 |
Run Time (Mins) |
65 |
30 |
28 |
19 |
15 |
13 |
11 |
8 |
7 |
6 |
Table 26-7 Estimated Load Times of ABCEG601-11 (Part Number 700247-094-PT)
Load Item | 10% Load Time | 20% Load Time | 30% Load Time | 40% Load Time | 50% Load Time | 60% Load Time | 70% Load Time | 80% Load Time | 90% Load Time | 100% Load Time |
---|---|---|---|---|---|---|---|---|---|---|
Volts |
122 |
122 |
121 |
121 |
121 |
122 |
121 |
121 |
116 |
114 |
Amps |
0.35 |
0.69 |
1.04 |
1.39 |
1.74 |
2.07 |
2.44 |
2.78 |
3.26 |
3.66 |
Watts |
4 |
84 |
126 |
168 |
210 |
252 |
294 |
336 |
378 |
420 |
Run Time (Mins) |
90 |
55 |
39 |
30 |
24 |
18 |
14 |
11 |
19 |
7 |
Table 26-8 Estimated Load Times of ABCEG800-11 (Part Number 700247-095-PT)
Load Item | 10% Load Time | 20% Load Time | 30% Load Time | 40% Load Time | 50% Load Time | 60% Load Time | 70% Load Time | 80% Load Time | 90% Load Time | 100% Load Time |
---|---|---|---|---|---|---|---|---|---|---|
Volts |
118 |
119 |
118 |
118 |
117 |
119 |
118 |
118 |
118 |
120 |
Amps |
0.44 |
0.87 |
1.32 |
1.76 |
2.21 |
2.63 |
3.08 |
3.52 |
3.94 |
4.36 |
Watts |
5 |
110 |
165 |
224 |
280 |
335 |
395 |
450 |
500 |
560 |
Run Time (Mins) |
77 |
46 |
32 |
23 |
17 |
14 |
11 |
10 |
8 |
6 |